EP-8000-4
Electronic To Pneumatic Transducer
by
done_outline8888 in stock
addShow Locations
removeHide Locations
High Volume, Relay Output, 4 To 20 mA DC Input Range, 3 To 15 psig Factory Output Range.
Features
Compact Simple Design
Hypodermic Needle Test Point Access
Factory Set, Fully Adjustable Zero And Span
High Accuracy With Low Hysteresis
Technical Details
Sensitivity:
0.3 psig/psig (0.3kPa/kPa)
Air Capacity:
Low volume models: 12.3 ml/s (45 scim) max. (value specified for dead-ended loads or with controlled devices/applications with a max. air consumption of 2.7 ml/s [10 scim])
Operating Temperature:
41° to 122? (5° to 50?)
Operating Humidity:
10 to 90% RH, non-condensing
Mounting:
Surface mounted or installed on a valve pneumatic actuator
Pressure:
18 to 25 psig (126 to 175 kPa); nominal 20 psig (140 kPa); air supply must be clean, dry, and oil free