Characterized Control Valve, Forged Brass, Nickel Plated Brass Body, Stainless Steel Ball And Stem,Valve Actuator, Modulating Control, Non-Spring Return, 100 To 240 VAC, For 2 To 10 VDC Or 4 To 20 mA.
Features
Valve Is Typically Used In Air Handling Units On Heating Or Cooling Coils, And Fan Coil Unit Heating Or Cooling Coils
Valve Is Suitable In Use In A Hydronic System With Variable Or Constant Flow
Ball Valve Design Offers Self-Cleaning And Zero Leakage
Rated For Water Temperatures Up To 250 F
Technical Details
Service
Chilled, Hot Water, Up To 60% Glycol
Flow Characteristic
A-Port Equal Percentage, B-Port Modified For Constant Common Port Flow
Operating Conditions
0 F To 250 F (-18 C To 120 C)
Close-Off Pressure
200 psi
Power Consumption
4 W Running, 1 W Holding
Operating Conditions
-22 F To 122 F (-30 C To 50 C)
Electrical Connection
3 ft. 10 ft. 16 ft. And 18 GA Appliance Cable With 1/2 in. Conduit Connector